So #OctopusEnergy surveyed our house yesterday and decided that they couldn't sell us a #HeatPump because they don't have one powerful enough. (Their maximum is 11kW.) There were no suggested remediations — we've already insulated everything — which means they should have known from the floor plan that they couldn't help us and saved everyone's time. 🙄
It's a long shot, I know, but does anyone have a technical contact inside #HeatGeeks? I don't want to spend £375 and another month on a survey, only to be told they can't help either. They don't reply usefully to email. Apparently, I could contact some technical people via Facebook, but I don't have a Facebook account because I don't hate myself.
@CppGuy I only have a hot water heat pump and live in a hot climate, so naive. Is the system designed to heat your entire house? If it's so cold 11kW is not enough, could you only heat part of your house?
When I visited family in the UK, to save money they only set their gas oil heaters to heat a few rooms at a time.
You'll probably need 3 phase power to go above 11kW.
@dean
Yes, the system is designed to heat the whole house.
I have no experience of running a heat pump but, from what I read on #HeatGeek, using a heat pump to heat only some rooms and leave others cold is a false economy:
https://www.heatgeek.com/why-not-to-zone-heat-pumps-or-boilers/
The 14kW #HeatPump that a local company proposes to install draws a maximum of 5.71kW, which is about 25A, so we should manage to avoid 3-phase, even if we need a 16kW heat pump, which ought to draw less than 30A. Most UK houses have 100A main fuses. (Ours is 80A, but I'm told that the upgrade is usually free of charge.)